← Back to Index
CZY (czy0126)ECADConfidence: Medium

An older audit still said the 50 V case had not run, but it had. The fault sim collapsed at 7.57 ms, so only the prefix is valid, and the resonant inductor at two turns hits about 0.33 T against a 0.279 T limit. The PR adds a risk register built from the committed results that keeps six P0 items blocked, and refuses to call a sim done unless the log shows elapsed time and the measured points.

Impact Analysis

Persona
Electrical Engineer
Team Size Impact
5x Multiplier
Prototype Delay
3 Days
Est. Annual Cost
$30,000
  • 1 user · 1 month240 min
  • Rest of team960 min
  • Rest of year13,200 min

monthly_minutes × 12 × team_multiplier ÷ 60 × $75/hr = $30k/yr

$75/hr assumed rate.

Annual team-minutes decomposed from the reported monthly inputs.

Evidence & Sources

1 Sources

Analyst Notes

From the Grok pain-radar digests, Nov 1-2 2026 (Nov 1 8:41 AM ET through Nov 2 7:41 AM ET digests plus the Haitch editions). Verified live 2026-11-02: issue/PR read; title and state confirmed.