erpnext_enhancements (sapphirefountains)ECADConfidence: Medium
sapphirefountains Fountain Designer used 125 percent of motor FLA as the breaker, which is the NEC 430.22 conductor rule, not the 430.52 breaker maximum. Fixing it changes real outputs: a 5 HP 230 V pump goes from 35 A to 70 A, a 30 A motor from 40 A to 80 A, and one service main goes from 70 A to 90 A. The water_calc AI tool description said 125 percent breaker too.
From the Grok pain-radar digests, Nov 1-2 2026 (Nov 1 8:41 AM ET through Nov 2 7:41 AM ET digests plus the Haitch editions). Verified live 2026-11-02: issue/PR read; title and state confirmed.