sapphirefountains Fountain Designer used 125 percent of motor FLA as the breaker, which is the NEC 430.22 conductor rule, not the 430.52 breaker maximum. Fixing it changes real outputs: a 5 HP 230 V pump goes from 35 A to 70 A, a 30 A motor from 40 A to 80 A, and one service main goes from 70 A to 90 A. The water_calc AI tool description said 125 percent breaker too.

Impact Analysis

Persona
Electrical Engineer
Team Size Impact
5x Multiplier
Prototype Delay
3 Days
Est. Annual Cost
$30,000
  • 1 user · 1 month240 min
  • Rest of team960 min
  • Rest of year13,200 min

monthly_minutes × 12 × team_multiplier ÷ 60 × $75/hr = $30k/yr

$75/hr assumed rate.

Annual team-minutes decomposed from the reported monthly inputs.